H = p/(ρg)   and   p = ρgH

Near 20 °C with density about 998.2 kg/m³, 1 m of water is about 9.79 kPa and 1 ft of water is about 0.433 psi. Rounded field factors are useful only when their assumptions are understood.

Quick table near 20 °C

PressureMetres of waterFeet of water
10 kPa1.02 m3.35 ft
100 kPa10.22 m33.53 ft
1 bar10.22 m33.53 ft
10 psi7.03 m23.07 ft
50 psi35.16 m115.35 ft

Gauge position and elevation

A gauge reading changes with elevation even in the same static water column. Record the gauge elevation and use pressure head plus elevation head consistently. Absolute pressure is required for vapor-pressure and NPSH work; most delivery-pressure calculations use gauge pressure.

Reference boundary. Do not convert an indicative value into a universal design, health or legal requirement. Check the cited source, laboratory context, certified claim and applicable jurisdiction.