What this tool does

Separate useful hydraulic power from pump-shaft and motor input power so efficiency assumptions are visible.

When to use it

Use it after flow and total head are defined and when a pump or scenario efficiency can be read from a manufacturer curve or measured.

Inputs and supported units

Each labelled field explains the quantity it expects. Unit-system changes convert existing numeric entries once and keep calculations on a single SI internal basis. Supported shared units include L/min and GPM, metres and feet, kPa and psi, millimetres and inches, kW and hp, and °C and °F as relevant.

Calculation or decision method

Phydraulic = ρgQH
Pshaft = Phydraulicpump
Pelectrical = Pshaftmotor

How to interpret the result

Read the primary result with the supporting breakdown and warning. A plausible number is not evidence that every input, operating case or design constraint has been included.

Worked example

At 120 L/min and 50 m head with 70% pump efficiency and 90% motor efficiency, estimated electrical input is about 1.56 kW.

Assumptions

Steady water flow; entered efficiencies apply at the duty point; direct drive with no additional drive loss.

Limitations

No motor part-load curve, service factor, starting current, drive loss or variable-speed map is included.

Safety and review boundary. Do not size the motor from this single number. Check the complete manufacturer power curve and applicable electrical requirements.